IE3 · 3-phase

EM3-180M-2-22

IE3 premium efficiency motor · 22 kW · 2 pole · 2950 rpm

IE32 poleFrame 180M400/690 V · 50 HzIP55 · IC411Duty S1SF 1.15 at 50 HzBIS IS 12615:2026SF 1.25 at 460 V 60 HzCE
Request a quote
IEC 180M · 400/690 V
IE3 premium efficiency motor
Representative model from frame 180M dimensions
Tap a partDrag to rotate · scroll to zoom
22kWRated output · 50 Hz
2950rpmRated speed
93.6%Efficiency, full load
71.3NmRated torque
38.1ACurrent at 400 V
0.89Power factor
116kgWeight, B3
2.2× MNStarting torque

Performance · 50 Hz, tested values

Output22 kW
Poles · synchronous speed2 · 3000 rpm
Rated speed2950 rpm
Rated torque MN71.3 Nm
Current at 230 V–
Current at 400 V38.1 A
Current at 690 V22.1 A
Current at SF 1.15, 400 V42.7 A
Efficiency 100 / 75 / 50 %93.6 / 93.6 / 93.1
Power factor 100 / 75 / 50 %0.89 / 0.85 / 0.77
Efficiency classIE3 (IEC 60034-30-1)
Locked-rotor torque MA/MN2.2
Starting current IA/IN9.5
Breakdown torque MK/MN4
Pull-up torque MS/MN2.1
Rotor inertia J0.09 kgm²
Sound pressure LPA at 1 m68 dB(A)
InsulationClass F, temperature rise class B
Enclosure · coolingIP55 · IC411 TEFC
Ambient−20 °C to +40 °C
Service factor1.15 at 400 V 50 Hz (S1)
Bearings DE / NDE6310ZZ / 6308ZZ

Torque–speed curve indicative

1×2×3×4×5× MAMKMN0750150022503000speed · rpmtorque ÷ MN

Drawn through the catalogue points MA, MS, MK and MN. Request the tested curve for your application.

Part-load performance

6070809010093.693.693.1100 % load75 % load50 % load Efficiency %cos φ × 100

Efficiency determined to IEC 60034-2-1. Values on a 400 V winding (230 V for single-phase), subject to IEC tolerances.

60 Hz · for North America

Supply460 V · 60 Hz
Output (calculated)25.3 kW · 33.93 HP
Nameplate HP30 HP
Speed3540 rpm
Torque50.34 lb-ft · 68.25 Nm
Full-load amps at nameplate HP≈ 34.7 A
Service factor1.25 · heat-run verified
SF amps≈ 41.3 A

About these values

Calculated from EMPD tested 50 Hz / 400 V data (output × 1.15, speed × 1.2) and confirmed by test on order with a 60 Hz test certificate. SF 1.25 proven by heat run at type test; report supplied at first-article approval. Continuous-duty (S1) motors sold in the US must meet NEMA Premium efficiency and be DOE-certified. Please contact EMPD to discuss.

Frames are IEC metric; NEMA frames 56C to 256T built to MG 1 on request. Please confirm certification requirements (e.g. UL / CSA) at enquiry.

Export programme

Dimensions · IM B3, frame 180M

L 667CBH 180EA 279

Schematic outline for orientation, not to scale for manufacture. Request the certified drawing (PDF / DXF / STEP) with your enquiry.

AFoot hole spacing, end279 mm
BFoot hole spacing, side241 mm
CShaft shoulder to foot hole121 mm
HShaft centre height180 mm
KFoot hole diameter15 mm
LOverall length667 mm
ACBody diameter358 mm
HDOverall height440 mm
DShaft diameter48 mm
EShaft length110 mm
MFlange B5 · pitch circle300 mm
NFlange B5 · spigot250 mm
PFlange B5 · outside diameter350 mm
SFlange B5 · hole diameter18.5 mm

Mountings B3, B5, B14, B35 and B34 on every rating. Shaft tolerance to IEC 60072. NEMA frames 56C to 256T built to MG 1 on request.

Let’s build your motor.

Send us output, speed, supply, mounting, duty and quantity. Our engineers reply with a recommendation and a quotation.